Shenzhen Qianhai Lensen Technology Co., Ltd

Lensen help your system link faster

Manufacturer from China
Verified Supplier
7 Years
Home / Products / Digital Signal Isolator /

Resistance Digital Signal Isolator Transducer 0-5KΩ Input To 4-20mA 0-5V Output Converter

Contact Now
Shenzhen Qianhai Lensen Technology Co., Ltd
Visit Website
City:shenzhen
Province/State:guangdong
Country/Region:china
Contact Person:MsSunny
Contact Now

Resistance Digital Signal Isolator Transducer 0-5KΩ Input To 4-20mA 0-5V Output Converter

Ask Latest Price
Brand Name :LS
Model Number :LS-TU-R
Certification :CE
Place of Origin :China
MOQ :1pc
Price :negociate
Payment Terms :T/T, Western Union, Paypal
Supply Ability :10000pcs
Delivery Time :3-6 days
Packaging Details :standard
Input :0-5KΩ resistane
Output :4-20mA; 0-20mA; 0-5V; 0-10V
Channels :1 input 1 output
Power supply :24V DC
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Resistance signal transducer 0-5KΩ input to 4-20mA or 0-5V output

Input

Input signal: resistance signal, resistance range: 0-5KΩ

Incentive method: built-in precision constant current source excitation

Output

Output signal: 4-20mA; 0-20mA; 0-5V; 0-10V

Maximum output current: 35mA

Output load resistance: RL ≤ 500Ω (when the output is a current signal);

RL>10KΩ (when the output is a voltage signal)

Note: The user can specify the current output or voltage output when ordering.

Basic parameters

Power: DC24V, voltage range: DC18-36V

Current consumption: ≤35mA (one input and one output, 24V power supply, 20mA output)

Basic accuracy: ±0.1 %F.S.

Temperature drift: 0.005% F.S./°C

Response time: ≤10mS (0-90%) (TYP)

Power protection: reverse power protection

Insulation strength: 1500V AC / 1min (between input, output, and power)

Insulation resistance: ≥100MΩ (between input, output, and power)

Operating temperature range: -20~+55 degrees

Electromagnetic compatibility: in accordance with GB/T 18268 (IEC61326-1)

Applicable field devices: two-wire resistor

Parameter
LS-TU-R X X X Remarks
Channel setting 1 One input one output

INPUT Setting

A 0-500Ω
B 0-1KΩ
C 0-5KΩ
OUTPUT Setting 1 4-20mA
2 0-20mA
5 0-5V
7 0-10V
Note: please confirm what kind of input signal and output signal do you need when you place order

Resistance Digital Signal Isolator Transducer 0-5KΩ Input To 4-20mA 0-5V Output Converter

Resistance Digital Signal Isolator Transducer 0-5KΩ Input To 4-20mA 0-5V Output Converter

Inquiry Cart 0